The Novus Micro Series provides constant, reliable backup power for Access Control, Security Public Utility and Telecommunications applications in a compact all-in-one enclosure. The Novus Micro UPS Series provides the same functionality as the Novus FXM Series, for lower power applications in a single, easy to install cabinet. Optional add-on battery cabinets support applications where longer backup times are required. Each power level is available in either North American (120 VAC/60 Hz) or International (230 VAC/50 Hz) variants.
Kit Contains:
|
Qty |
P/N |
Description |
|
1 |
017-221-25 |
Novus FXM Micro 300; One Box Solutions with Weatherproof Enclosure , Requires Battery Cable Kit and Batteries, 60Hz, 300 VA/W, 120Vi, TB, 24VDC |
|
1 |
870-602-23 |
BCK- 2 x 85GXL Micro 300; Battery Cable Kit, Novus Micro 300, 24VDC, 2 x 85GXL |
|
1 |
189-223-10 |
Heater Mat, 120V, 8" x 13", 55W |
|
2 |
181-198-10 |
Battery, 12V, 50Ah@20Hr, AlphaCell 85GXL-HP Silver Alloy | |
Product Family Features:
- Clean, uninterruptible backup power ensures your system will remain up and running during power outages
- Wide range Automatic Voltage Regulation without going to batteries extends battery life, even during periods of surge or sag in voltage from utility power.
- External communications via RS-232 port or (optional) SNMP Ethernet interface provides local or remote monitoring control
- Independently programmable control and report relays allow tracking and controlling of key functions1
- User-friendly LCD display allows at-a-glance± monitoring and troubleshooting2
- Event and alarm logging with time and date stamping simplifies and accelerates troubleshooting
- A wide operating temperature range of -40 to 74 C (-40 to 165 F)3 is suitable for the most extreme operating environments
- Temperature compensated battery charging protects batteries from over charging at extreme temperatures
1 This feature is available on the Novus Micro 1000 Model only. 2 This feature is optional for the Novus Micro 300 model. 3 This applies to the UPS module only. Batteries may require a heater mat at lower temperatures. Output power derates after 50 C.
Specifications:
|
Nominal |
|
Power Module |
US |
|
Nominal Voltage |
120 VAC |
|
Nominal Frequency |
60 Hz |
|
Input Current |
5.4 A |
|
Output Current |
2.5 A |
|
Output Power at 50ўЄC |
300 W/VA |
|
Programmable Relays |
2 |
|
Battery String Voltage |
24 VDC |
|
Performance |
|
Input Voltage Range (120 VAC) |
85 to 175 VAC w/o going to batteries |
|
Input Voltage Range (230 VAC) |
Input Voltage Range (230 VAC) |
|
Output Voltage Regulation |
Ўѕ10% over full input voltage range |
|
Output Voltage Waveform |
Pure sine wave |
|
Typical Efficiency (full resistive load) |
>92% (line mode) |
|
Typical Output Voltage THD |
<3% |
|
Typical Transfer Time: |
<5ms |
|
Audible Noise @ 1m |
45dBA |
|
Environmental |
|
Operating Temperature |
-40 to 74 C (-40 to 165 F)* |
|
Storage Temperature |
Storage Temperature |
|
Operating Altitude** |
12,000 ft / 3658 m |
|
Operating Humidity |
Up to 95% |
|
* This applies to the UPS module only. Batteries may require a heater mat at lower temperatures. Output power derates after 50oC. ** Derate 2ўЄC per 1000 ft (305 m) above 4500 ft (1370 m) |
|
Mechanical |
|
Width |
14.1 in / 358 mm |
|
Height |
19.67 in / 499.6 mm |
|
Height |
11.56 in / 293.6 mm |
|
Unit Weight* |
44 lb / 20 kg |
|
* Stated weight does not include batteries. |
|
Agency Compliance |
|
Electrical Safety: UL1778, CSA 22.2 No. 107.3, EN50091-1-2, EN60950 EMI: Level A FCC, CISPR22, EN55022 Marks: CCSAUS , CE* |
|
* CE applies to 230 VAC version only |
Models Dimensions Comparison Chart:

|